Date: October 2012

Company: KSB / Santiago – Metropolitan area

CH dry three phase autotransformer, auto refrigerated through natural air, protective cabinet, indoors, vacuum impregnated in dielectric varnish. H class designed, built and tested according ANSI C 57.12.91 norms and ANSI C 57.12.01.

  • Autotransformer general characteristics

Potential: 600 kVA

Raise of temperature: 115 ºC

Service altitude: 1000 m.a.s.l.

Frequency: 50 – 60 Hz

Autotransformer connection: Three phase

Connection group: Yyn0

Impendency: <3%

Nº Phases: 3

Nominal primary voltage: 380 Volts (input)

Secondary voltage: 380 – 460 – 575 – 660 – 1000 Volts (output)

Refrigeration: natural air

K Factor: 2

Losses: Normal

  • Tests done to autotransformers

Routine tests indicated in ANSI C 57.12.01 norms will be realized. Also pressure and sealing tests.

  • Autotransformers accessories

– Input and output connections for taps.

– IP22 protection cabinet.

– Ground connection.

– Eyebolts

– Steel characteristic plates.

– Anchor base to floor or platform.