Date: December 2011

Company: SRF / Santiago – Metropolitan Region.

A work of maintenance to prevent was realized to a distribution transformer. The service:

– Measuring of the voltages of service (MULTITESTER).

– Measuring of protection and service meshes, with energized transformer and a measuring instrument induction type. (GROUND RESISTANCE CLAMP-ON)

– Dis-energization of transformer and grounding of A.T. networks.

– Extraction of an oil sample to analise the acidity index (ASTM?D974), density (ASTM?D1298) and dielectric rigidness (ASTM?D877).

– Measures of Relationship og Transformation (TTR) in position of taps of service.

– Measuring of Resistance of Insulation to coils with Megger 5000 Volts.

– Cleaning, revising and tightening high and low voltage bushings with the convenient pressure of gear.

– Revision of the situation of packages and tightening of perneria, crossheads, supported beams of the transformer, pond and grills.

– Revision of the draining valve, tap changer, dielectric oil level, grounding connections, temperature indicator, jar and silica gel and other instruments of TF control.

– Revision of painting and oxide state in case there were some left and the consequent cleaning.

– Revision of fuse disconnectors state or MT Cell, mufa and perneria.

– Revision of Boards and BT Cells, interrupter and perneria.

– Activation S/E with voltage verification.

– Realization of a report with the conclusions and recommendations to each transformer. In case that the professionals must take part to normalize the operation, to this report the quoted works will be attached.